Battery Energy Storage Systems.

CORE hero background

418 kWh

CORE

3-layer

Unbalanced Load Support

Intelligent

Liquid Cooling

BMS + EMS

Integrated

Real-Time

Remote Monitoring

Air-Cooled Energy Storage System

Higher capacity on the same engineering platform. Designed for larger commercial and industrial loads - data centres running at scale, manufacturing plants with continuous shift operations, hospital campuses where stored energy is also emergency infrastructure. At this capacity, the financial case is direct: the stored energy pays for the system within a predictable number of billing cycles. The decision is not whether to invest. It is when.

DC Side

Cell Type

LFP / 314 Ah

Pack Configuration

52.248 kWh / 1P52S

System Configuration

418 kWh / 1P416S

Rated DC Voltage

1331.2 V

DC Voltage Range

1164.8 ~ 1497.6 V

Max. Charge/Discharge Rate

418 - 40

0.25 P

418 - 69

0.5 P

418 - 80

0.5 P

Max. Depth of Discharge

100% (25 ± 2°C)

AC Side

Rated Output Power

418 - 40

100 kW

418 - 69

215 kW

418 - 80

210 kW

Rated AC Voltage

418 - 40

400 V

418 - 69

690 V

418 - 80

800 V

AC Voltage Range

-15% ~ +10%

Grid Type

3W + PE

Rated Frequency

50 Hz / 60 Hz

Power Factor

0.99 / -1 ~ +1

THDi

≤ 3%

DC Ratio

< 0.5% Ipn

General

Max. Round Trip Efficiency

89%

Cycle Life

≥ 8,000 cycles

Communication

Modbus TCP/IP

Fire Suppression System

Aerosol

Ingress Rating

IP55

Cooling

Liquid cooling + Forced air cooling

Operating Temperature

-25°C ~ 55°C (Derating after 45°C)

Anticorrosion Rating

C4 (C5 optional)

Humidity

0 ~ 95% RH (non-condensing)

Noise

≤ 80 dB

Altitude

3000 m (Derating above 2000 m)

Dimensions (W*D*H)

1,500*1,350*2,400 mm

Weight

3,800 kg